Wiring Configurations For Start/Stop - Danfoss VLT AQUA Drive FC 202 Design Manual

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Application Examples
FC
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
4 - 20mA
COM
39
U - I
A53
Table 12.4 Wiring Configuration for Analog Speed Reference
(Current)

12.3 Wiring Configurations for Start/Stop

FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 12.5 Wiring Configuration for Start/Stop Command with
Safe Torque Off
MG22B222
Design Guide
Parameters
Function
Setting
Parameter 6-12 T
4 mA*
erminal 53 Low
Current
Parameter 6-13 T
20 mA*
erminal 53 High
Current
Parameter 6-14 T
0 RPM
erminal 53 Low
Ref./Feedb. Value
Parameter 6-15 T
1500 RPM
erminal 53 High
Ref./Feedb. Value
*=Default value
Notes/comments:
Parameters
Function
Setting
Parameter 5-10 T
[8] Start*
erminal 18
Digital Input
Parameter 5-12 T
[0] No
erminal 27
operation
Digital Input
Parameter 5-19 T
[1] Safe
erminal 37 Safe
Torque Off
Stop
Alarm
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
Danfoss A/S © 01/2018 All rights reserved.
Speed
Start/Stop (18)
Figure 12.1 Start/Stop with Safe Torque Off
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 12.6 Wiring Configuration for Pulse Start/Stop
Speed
Latched Start (18)
Stop Inverse (27)
Figure 12.2 Latched Start/Stop Inverse
Parameters
Function
Setting
Parameter 5-10 T
[9] Latched
erminal 18
Start
Digital Input
Parameter 5-12 T
[6] Stop
erminal 27
Inverse
Digital Input
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
199