8.3 Wiring for Start/Stop

FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
Table 8.5 Start/Stop Command
MG06I102
Operating Guide
Parameters
Function
Setting
Parameter 5-10 Termin
[8] Start*
al 18 Digital Input
Parameter 5-12 Termin
[19]
al 27 Digital Input
Freeze
Reference
Parameter 5-13 Termin
[21]
al 29 Digital Input
Speed Up
Parameter 5-14 Termin
[22]
al 32 Digital Input
Speed
Down
* = Default value
Notes/comments:
Parameters
Function
Setting
Parameter 5-10
[8] Start*
Terminal 18
Digital Input
Parameter 5-12
[0] No
Terminal 27
operation
Digital Input
* = Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
Danfoss A/S © 06/2018 All rights reserved.
Speed
Start/Stop (18)
Illustration 8.2 Start/Stop Command
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 8.6 Pulse Start/Stop
Speed
Latched Start (18)
Stop Inverse (27)
Illustration 8.3 Latched Start/Stop Inverse
Parameters
Function
Setting
Parameter 5-1
[9] Latched
0 Terminal 18
Start
Digital Input
Parameter 5-1
[6] Stop
2 Terminal 27
Inverse
Digital Input
* = Default value