Mechanical Installation

4 Mechanical Installation

4.1 Items Supplied

Items supplied can vary according to product configu-
ration.
4
4
Make sure the items supplied and the information
on the nameplate correspond to the order confir-
mation.
Visually check the packaging and the drive for
damage caused by inappropriate handling during
shipment. File any claim for damage with the
carrier. Retain damaged parts for clarification.
VLT
1
T/C: FC-102N500T4E20H2XGC7XXSXXXXAXBXCXXXXDX
2
P/N: 135N6991
3
500 kW / 650 HP
4
IN: 3x380-480V 50/60Hz 848/752 A
OUT: 3x0-Vin 0-590Hz 880/780 A
5
CHASSIS/IP20
Tamb. 40 C/104 F at Full Output Current
Max Tamb. 55 C/131 F at Full Output Current Derating
SCCR 100 kA at UL Voltage range 380-480 V
ASSEMBLED IN USA
6
1
Type code
2
Code number
3
Power rating
Input voltage, frequency, and current (at low/high
4
voltages)
Output voltage, frequency, and current (at low/high
5
voltages)
6
Discharge time
Illustration 4.1 Product Nameplate for E4h Enclosure (Example)
NOTICE
Removing the nameplate from the drive can result in the
loss or warranty.
12
VLT® HVAC Drive FC 102
HVAC Drive
R
www.danfoss.com
S/N:
123456H123
Listed 36U0 E70524 IND. CONT. EQ.
UL Voltage range 380-480 V
Danfoss A/S
6340 Nordborg
Denmark
CAUTION - ATTENTION:
See manual for special condition / prefuses
Voir manuel de conditions speciales / fusibles
`
WARNING - AVERTISSEMENT:
Stored charge, wait 40 min.
Charge residuelle, attendez 40
`
Danfoss A/S © 01/2017 All rights reserved.

4.2 Tools Needed

Receiving/unloading
I-beam and hooks rated to lift the weight of the
drive. Refer to chapter 3.2 Power Ratings, Weights,
and Dimensions.
Crane or other lifting aid to place the unit into
position.
Installation
Drill with 10 mm or 12 mm drill bits.
Tape measurer.
Various sizes of Phillips and flat bladed
screwdrivers.
Wrench with relevant metric sockets (7–17 mm).
Wrench extensions.
Torx drives (T25 and T50).
Sheet metal punch for conduits or cable glands.
I-beam and hooks to lift the weight of the drive.
Refer to chapter 3.2 Power Ratings, Weights, and
Dimensions.
Crane or other lifting aid to place the drive onto
pedestal and into position.

4.3 Storage

Store the drive in a dry location. Keep the equipment
sealed in its packaging until installation. Refer to
chapter 9.4 Ambient Conditions for recommended ambient
temperature.
Periodic forming (capacitor charging) is not necessary
during storage unless storage exceeds 12 months.
MG16O102