Wiring Configuration Exampl...
7.4 Wiring for a Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
•
To meet PELV insulation requirements, use only
thermistors with reinforced or double
insulation.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
7
7
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 7.9 Motor Thermistor
58
VLT® HVAC Drive FC 102
Parameters
Function
Setting
Parameter 1-90
[2] Thermistor
Motor Thermal
trip
Protection
Parameter 1-93
[1] Analog
Thermistor
input 53
Resource
* = Default value
Notes/comments:
If only a warning is desired, set
parameter 1-90 Motor Thermal
Protection to [1] Thermistor
warning.
Danfoss A/S © 01/2017 All rights reserved.
7.5 Wiring for Regeneration
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 7.10 Regeneration
Parameters
Function
Setting
Parameter 1-90
100%*
Motor Thermal
Protection
* = Default value
Notes/comments:
To disable regeneration,
decrease parameter 1-90 Motor
Thermal Protection to 0%. If the
application uses motor brake
power and regeneration is not
enabled, the unit trips.
MG16O102