H1 Digital Inputs - YASKAWA E7N Technical Manual

Drive/bypass
Table of Contents

Advertisement

F6-05 Current Scaling via Communication Option PCB
Setting
0
A Display (factory default)
1
100%/8192 (Drive Rated Current)
A communication option card can read the Drive's DPRAM to access the current monitor. The format of the current reading in
the DPRAM will be determined by parameter F6-05.
F6-05= "0: A Display"
F6-05= "1: 100%/8192 (Drive Rated Current)"

H1 Digital Inputs

H1-01 Drive Terminal S3 Function Selection
H1-02 Drive Terminal S4 Function Selection
H1-03 Drive Terminal S5 Function Selection
H1-04 Drive Terminal S6 Function Selection
H1-05 Drive Terminal S7 Function Selection
Setting Range:
0 to 6E
Factory Default: H1-01= "70: Bypass Drv Envl" This is one of the special parameter settings required by the Bypass logic
H1-02= This is one of the special parameter settings required by the Bypass logic circuit. See Table 5.2
H1-03= This is one of the special parameter settings required by the Bypass logic circuit. See Table 5.2.
H1-04= "4: Multi-Step Ref 2" (2 Wire)
"3: Multi-Step Ref 1" (3 Wire)
H1-05= "6: Jog Freq Ref " (2 Wire)
"4: Multi-Step Ref 2" (3 Wire)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Current is a decimal number corresponding to actual Amperes
8192 = 100% of Drive rated output current
circuit. See Table 5.1.
Programming 5 - 49
Current reading is a number where