2 CALCULATION OF SETTINGS
Table 2–7: PROTECTION SETTINGS GUIDE (Sheet 1 of 7)
No.
Mnem onic
Z1DISTANCE
101
Z1PHASE
102
Z1PHREACH
104
Z1P_TIME
Z2 DISTANCE
201
Z2PHASE
202
Z2PHREACH
203
Z2PCHARANG
204
Z2TIMER
Z2P_TIM E
205
Z3DISTANCE
301
Z3PHASE
302
Z3PHREACH
303
Z3PCHARANG
304
Z3P_TIME
Z4DISTANCE
401
Z4PHASE
402
Z4PHREACH
403
Z4PCHARANG
404
Not Used
405
Z4_TIMERS
406
Z4P_T IM E
see TABLE NOTES on page 2–43 for footnote explanation
GE Power Management
Description
Z1 Phase Distance
Z1 Phase Reach
Z1 Phase Timer
Z2 Phase Distance
Z2 Phase Reach
Z2 Phase Characteristic
Angle
Z2 Timer
Z2 Phase Timer
Z3 Phase Distance
Z3 Phase Reach
Z3 Phase Characteristic
Angle
Z3 Phase Timer
Z4 Phase Distance
Z4 Phase Reach
Z4 Phase Characteristic
Angle
Z4 Timers
Z4 Phase Timer
LPS-O Line Protection System
2.5 REFERENCE TABLES

2.5.2 PROTECTION SETTINGS GUIDE

Range (5A)
Range (1A)
NO, YES
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
0.00 to 10. sec.
0.00 to 10. sec.
step 0.01
step 0.01
NO, YES
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
90 to 120 deg.
90 to 120 deg
step 5
step 5
NO, YES
NO, YES
0.00 to 10.0 sec.
0.00 to 10.0 sec.
step 0.01
step 0.01
NO, YES
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
90 to 120 deg.
90 to 120 deg
step 5
step 5
0.00 to 10.0 sec.
0.00 to 10.0 sec.
step 0.01
step 0.01
NO, YES
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
80 to 120 deg.
80 to 120 deg
step 5
step 5
NO, YES
NO, YES
0.00 to 10.0 sec.
0.00 to 10.0 sec.
step 0.01
step 0.01
Default
2
YES
5.40Ω at 5A
27.0Ω at 1A
0.0 sec.
YES
9.00Ω at 5A
45.0Ω at 1A
90 deg.
YES
1.0 sec.
YES
12.0Ω at 5A
60.0Ω at 1A
90 deg.
2.0 sec.
YES
18.0Ω at 5A
90.0Ω at 1A
90 deg.
YES
0.05 sec.
2-
37