2 CALCULATION OF SETTINGS
Table 2–9: PROTECTION SETTINGS DATA SHEET (Sheet 3 of 7)
No.
Mnem onic
615
51GTIMDIAL
616
DEFTIMDELY
617
51G_RESET
VOLTAGE
701
RATEDVOLTS
702
PHASEOVER
703
PHOVPICKUP
704
PHOVTMDLY
705
FUSEFAIL
LINEPICKUP
801
LINEPICKUP
802
BYPASSTL3
803
I1PICKUP
REMOTEOPEN
901
REM O TEO PEN
902
TL20PICKUP
LINE OVERLD
1001
LIN EO VE R LD
1002
LEVEL1PU
1003
LEVEL2PU
1004
LEVEL1TDLY
1005
LEVEL2TDLY
see TABLE NOTES on page 2–53 for footnote explanations
GE Power Management
Description
51G Time Dial
Definite Time Delay
51G Reset Characteristic
Rated Per Unit Voltage
Select Phase Overvoltage
Phase Overvoltage Pickup
Phase Overvoltage Time
Delay
Potential Fuse Failure
Blocking
Select Line Pickup
Bypass Line Pickup Time
Delay
I1 Pickup
Select Remote Open
Detector
Remote Open Detector Time
Delay
Select Line Overload
Protection
Level 1 pickup current
Level 2 pickup current
Level 1 time delay
Level 2 time delay
LPS-O Line Protection System
2.5 REFERENCE TABLES
Range (5A)
Range (1A)
0.5 to 10.0
0.5 to 10.0
step 0.1
step 0.1
0.5 to 30.0 sec.
0.5 to 30.0 sec.
step 0.1
step 0.1
FAST,. EM
FAST, EM
100, 105,110,115,
100, 105, 110, 115,
120 volts
120 volts
NO, YES
NO, YES
0.0 to 1.4 p.u. volts
0.0 to 1.4 p.u. volts
step 0.01
step 0.01
0.0 to 10.0 sec.
0.0 to 10.0 sec.
step 0.01
step 0.01
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
1.0 to 15.0 amps
0.2 to 3.0 amps
step 0.1
step 0.1
NO, YES
NO, YES
10 to 100 msec.
10 to 100 msec.
step 1
step 1
NO, YES
NO, YES
2.5 to 20 amps
0.5 to 4.0 amps
step 0.1
step 0.1
5.0 to 40.0 amps
1.0 to 8.0 amps
step 0.1
step 0.1
10 to 200 sec.
10 to 200 sec.
step 1
step 1
10 to 99 sec.
10 to 99 sec.
step 1
step 1
User
Setting
2
2-
49