GE LPS-O Instruction Manual page 259

Line protection system
Table of Contents

Advertisement

12 ASCII COMMUNICATIONS
Table 12–3: ASCII COMMAND LIST
ASCII
Command Description
Command
Mnemonic
GROUP
INPuts
Request contact converter
status
MODEL
Retrieve the model
number, serial number,
and version of the relay
CRCcalc
Recalculates the CRC of
various settings groups
(this is primarily a
troubleshooting command
- it is used only where a
relay may have gone
through a loss power
during a settings change,
and the settings are
corrupted beyond the
ability of the relay to
correct).
STLINID
Allows the station and line
IDs to be changed
GE Power Management
(Sheet 4 of 7)
Lowest
Relay Prompt
Level
Password
Needed
SETTING
The active Protectioning Setting Group number is 1
To select a Setting Group enter Setting Group
Number ('1' - '4')
To select active setting group through Contact
Converter Inputs enter '0'
To quit press ESC
Enter your choice:
Are you sure (Y/N):? y
New Active Group = 3
VIEW
Contact Converter #0=0 ( SETTING GROUP BIT 0 )
Contact Converter #1=1 ( SETTING GROUP BIT 1 )
Contact Converter #2=1
Contact Converter #3=0
Contact Converter #4=0
Contact Converter #5=1
Contact Converter #6=0
Contact Converter #7=1
VIEW
MODEL: LPSDA35U143VE3S
VERSION: V0001.11
SETTINGS
CRCs are recalculated
SETTINGS
Station ID: Current Station ID
Line ID: Current Line ID
Do you want to change Station and/or
Line ID? (Y/N): y
Enter new Station ID (max. 32 characters): NEW
STATION ID
Enter new Line ID (max. 32 characters): NEW
FEEDER ID
Are you sure? (Y/N): y
LPS-O Line Protection Relay
12.1 INTRODUCTION
User Response
Enter digit from
0 to 4; enter
letter
None
(not assigned)
(not assigned)
(not assigned)
(not assigned)
(not assigned)
(not assigned)
None
None
Y to change, N
to exit; NEW
STATION ID or
ENTER to keep
current ID; NEW
FEEDER ID or
ENTER to keep
current ID; enter
letter
12
12-
5