GE LPS-O Instruction Manual page 80

Line protection system
Table of Contents

Advertisement

2.5 REFERENCE TABLES
Table 2–7: PROTECTION SETTINGS GUIDE (Sheet 4 of 7)
No.
Mnem onic
SCHEMETIMERS
1101
TL5PICKUP
2
1102
TL5DROPOUT
1103
TL6PICKUP
1104
TL6DROPOUT
LINEINFO
1201
PO SS EQ A N G
1202
CTRATIO
1203
PTRATIO
1204
TRSFMRTYPE
OS BLOCKING
1301
M O BZ O N E
1302
M O B C H A R A N G
1303
BLOCKWHAT
1304
BLOCKZ1
1305
BLOCKZ2
1306
BLOCKZ3
1307
BLOCKZ4
OS TRIPPING
1401
U S E_O ST
1402
NUMBRCHAR
1403
TRIPIN_OUT
1404
FWDREACH
see TABLE NOTES on page 2–43 for footnote explanation
2-
40
Description
BKR1 b sw Coord Timer PU
BKR1 b sw Coord Timer DO
BKR2 b sw Coord Timer PU
BKR2 b sw Coord Timer DO
Positive Sequence
Impedance Angle
CT Ratio
PT Ratio
Transformer Type
Coordinating Zone
MOB Characteristic Angle
Block during OS
Block all Zone 1 Functions
Block all Zone 2 Functions
Block all Zone 3 Functions
Block all Zone 4 Functions
Select OST
Select Number of
Characteristics
Trip Entering or Leaving Inner
OST Forward Reach
LPS-O Line Protection System
2 CALCULATION OF SETTINGS
Range (5A)
Range (1A)
0 to 200 msec.
0 to 200 msec.
step 1
step 1
0 to 200 msec.
0 to 200 msec.
step 1
step 1
0 to 200 msec.
0 to 200 msec.
step 1
step 1
0 to 200 msec.
0 to 200 msec.
step 1
step 1
25 to 90 deg.
25 to 90 deg.
step 1
step 1
1 to 5000
1 to 5000
step 1
step 1
1 to 7000
1 to 7000
step 1
step 1
NONE, YD1, YD5,
NONE, YD1, YD5,
YD7, YD11
YD7, YD11
ZONE2, ZONE3
ZONE2, ZONE3
30 to 130 deg.
30 to 130 deg.
step 1
step 1
BLKALL, BLKDIST,
BLKALL, BLKDIST,
BLKPHAS,
BLKPHAS,
BLKNONE
BLKNONE
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
2, 3
2, 3
IN, OUT
IN, OUT
0.1 to 75.0 ohms
0.5 to 375.0 ohms
step 0.1
step 0.5
Default
50 msec.
50 msec.
50 msec.
50 msec.
85 deg.
400 for 5A
2000 for 1A
3000
YD1
ZONE3
70 deg.
BLKALL
YES
YES
YES
YES
NO
3
OUT
15.0Ω at 5A
75.0Ω at 1A
GE Power Management

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lpsob35u23ve1n

Table of Contents