Fixed Frequency Setpoint Value (P10) - Eaton M-Max Series Operating Instructions Manual

Adjustable frequency drive
Hide thumbs Also See for M-Max Series:
Table of Contents

Advertisement

Parameters

Fixed frequency setpoint value (P10)

Fixed frequencies have a higher priority than frequency reference
values. They can be called individually, binary coded, or via the
digital inputs DI1 to DI6 or via the sequencing control program.
h
The maximum permitted set value for a fixed frequency is
limited by parameter P6.4 (maximum frequency).
A fixed frequency value can go below a minimum limit
frequency set at parameter P6.3.
h
The fixed frequency values can be changed during
operation (RUN).
Fixed frequency
You can set eight different fixed frequency setpoints (FF0 to FF7)
in the parameter group P10.
+24 V
6
7
Figure 92: Fixed frequencies FF1, FF2 and FF3 (= FF1 + FF2)
Figure 93: Example: Activation of the fixed frequencies in the factory setting with acceleration and deceleration ramps
104
8
9
10
14
DI1
DI2 DI3 DI4
f
P6.5
[Hz]
f
P6.4
max
(50 Hz)
20 Hz
15 Hz
10 Hz
0 Hz
DI3
FF1
DI4
DI1
a
P6.8 = 1
The fixed frequencies FF1 = 10 Hz, FF2 = 15 Hz and FF3 = 20 Hz
can be called via digital inputs DI3 (control signal terminal 10) and
DI4 (control signal terminal 14) in the factory setting.
Input (binary)
B0
B1
X
X
X
X
X
X
X
X
The change between the individual fixed frequency values is
completed with the acceleration and deceleration times set at P6.5
and P6.6. When the FWD or REV enables are switched off, the
output frequency is immediately blocked (uncontrolled coasting).
P6.8 = 1 causes the drive to perform a controlled deceleration a.
P6.6
a
FF3
FF1
FF2
FF3
FWD
04/10 MN04020001Z-EN
Fixed frequency
B2
(Factory setting)
FF0, P10.1 = 5 Hz, only if P6.2 = 0
FF1, P10.2 = 10 Hz
FF2, P10.3 = 15 Hz
FF3, P10.4 = 20 Hz
X
FF4, P10.5 = 25 Hz
X
FF5, P10.6 = 30 Hz
X
FF6, P10.7 = 40 Hz
X
FF7, P10.8 = 50 Hz
b
t [s]