PowerXL DM1 and DM1 Pro series VFD

Factory-set control terminal functions

Table 7. I/O connection.
External wiring Terminal
Short name
1
DI1
1
2
DI2
2
3
DI3
3
4
DI4
4
5
CMA
5
6
6
A
7
7
B
8
AI1+ 
8
9
AI1-
9
10
GND
10
11
AO1+
11
12
12
GND
13
13
10 V
14
14
24 V
15
15
STO_com
16
16
STO2
17
17
STO1
18
18
R1NO
19
19
R1CM
20
R1NC
20
21
R2NO
21
22
R2CM
22
Notes:
The above wiring demonstrates a SINK configuration. It is important that CMA is wired to ground (as shown by dashed line).
If a SOURCE configuration is desired, wire 24 V to CMA and close the inputs to ground. When using the +10 V for AI1, it is important to wire AI1- to ground (as shown by dashed
line).
 AI1+ support 10 K potentiometer.
Default
Name
Digital input 1
Digital input 2
Digital input 3
Digital input 4
DI1 to DI4 common
RS-485 signal A
RS-485 signal B
Analog input 1
Analog input 1 ground
I/O signal ground
Analog output 1
I/O signal ground
10 Vdc reference output
24 Vdc control output
Safe torque common
Safe torque Off 2
Safe torque Off 1
Relay 1 normally open
Relay 1 common
Relay 1 normally closed
Relay 2 normally open
Relay 2 common
Default setting
Description
Run forward
Starts the motor in the forward direction.
Run reverse
Start the motor in the reverse direction.
External fault
Triggers a fault in the drive.
Fault reset
Resets active faults in the drive.
Grounded
Allows for sourced input.
Fieldbus communication (Modbus RTU, BACNet).
Fieldbus communication (Modbus RTU, BACNet).
0 - 10 V
Voltage speed reference (programmable to 4 mA to 20 mA).
Analog input 1 common (ground).
I/O ground for reference and control.
Output frequency
Shows output frequency to motor 0 - 60 Hz (4 mA to 20 mA).
I/O ground for reference and control.
10.3 Vdc +/- 3%
10 Vdc reference voltage.
24 Vdc In/Out
Control voltage input/output (100 mA max.).
Safe torque Off common.
Safe torque Off 2 input.
Safe torque Off 1 input.
Run
Changes state when the drive is in the run state.
Fault
Changes state when the drive is in the fault state.
Instruction Leaflet
PUB53675
Effective June 2020
Default
EATON www.eaton.com
21