P Otentiometers - Besam ASSA ABLOY Swingmaster 900 Service And Installation Manual

Table of Contents

Advertisement

P otentiometers

8 7 B
HSC1
High Speed Closing from 90-0 degrees at
power failure.
HSC2
High Speed Closing from 90-10 degrees
at normal operation.
RUO
Reverse Upon Obstruction will make an
opening door stop if obstructed. Once
time delay has expired, the door will
close.
HLD
Hold force will balance the spring closing
force and keep the door still in any
position.
Hold force starts 9 or 18 second after
given impulse depending on the shunt
setting.
RMP
The Ramp down is a brake between
HSO and BCK to get a smooth or distinct
change from high speed to low speed.
BCK
Back Check is the low speed from 80 to
90 degrees.
HSO
High Speed Open from 0-80 degrees.
TD
Time Delay after loss of detection.
HOLD
Time delay before switching into hold
SHUNT
force (HLD).
Besam Entrance Solutions
Closing time can be adjusted from 7 to 5 seconds.
Counter clockwise (CCW) gives the lowest speed.
Closing time can be adjusted from 8 to 6 seconds.
CCW gives the lowest speed. Last 10 degrees of
closing is factory set at 1.5 seconds.
The required force to stop an opening door can be
adjusted from 15 lbs to 25 lbs depending on door
width and weight. Clockwise gives the lowest
force.
Note: If tripping breaker, see adjustments on page
37.
Force can be adjusted to overcome any of the
standard closing springs used. CCW gives the
lowest hold force.
CCW gives most brake.
CCW gives the lowest speed.
CCW gives the lowest speed.
Can be adjusted from 1.5 to 60 seconds.
Slave should be set to minimum. CCW gives the
lowest time.
9 seconds with shunt and 18 seconds without
shunt. Master and slave shunt to be set equal.
39
1/31/2008