(Figure 3-4: Manual Bypass Mode Diagram)
3.5
ECO Mode
After the UPS is manually set as ECO mode via the LCD, the UPS will work in Bypass mode
if bypass input voltage and frequency are within ±10% of the rated voltage and ±3Hz of the
rated frequency respectively. Otherwise, the UPS will run in On-Line mode. During ECO
mode, the UPS's tri-color LED illuminates green and the text 'ECO' appears in the upper
right corner of the LCD screen.
(Figure 3-5: ECO Mode Diagram)
33