Parallel Setting

Path:
→ Parallel Setting
Item
Parallel Group ID
Parallel ID
Common Battery
7.6.6

Dry Contact Setting

Path:
→ Dry Contact Setting
Input Dry
Contact No.
Input Dry Contact 1
Input Dry Contact 2
Input Dry Contact 3
Input Dry Contact 4
Ultron DPS Series
Enable or disable the high temperature alarm. If enabled, set
up the temperature.
Record the battery installation date.
Set up the battery replacement date.
The UPSs in parallel connection must be assigned the same
parallel group ID no. in order to let the outputs of the parallel
UPSs be put in parallel connection and let the loads be evenly
distributed among the parallel units.
If the parallel UPSs have different parallel group ID no., their
output signals might be synchronized but their outputs cannot
be connected in parallel.
The UPSs that need to be paralleled must be assigned the
same parallel group ID no. and different parallel ID no. in order
to let the parallel function work.
If the parallel UPSs that have the same parallel group ID no.
need to share common batteries, please select 'Enable' for the
'Common Battery' setup item. Otherwise, the function of
battery abnormality detection will fail. For more information
about common battery, please refer to 5.5 External Battery
Cabinet Connection Warnings.
Event Selection
1. None
2. Generator Status
3. Battery Ground Fail
4. External Battery Breaker Detection
5. Charge Off (Positive)
116
Description
Description
Set up NO
(normally open) or
NC (normally
closed) for each
input dry contact.