3.5
ECO Mode
After the UPS is manually set as ECO mode via the LCD, the UPS will work in Bypass mode
if bypass input voltage and frequency are within ±10% of the rated voltage and ±3Hz of the
rated frequency respectively. Otherwise, the UPS will run in On-Line mode. During ECO
mode, the UPS's tri-color LED illuminates green and the text 'ECO' appears in the upper
right corner of the LCD screen.
3.6
Frequency Conversion Mode
NOTE:
Frequency Conversion mode is only applicable to single UPS but not to parallel
UPSs.
After the UPS is manually set as Frequency Conversion mode via the LCD, the inverter will
automatically select 50Hz or 60Hz as the fixed output frequency. After the output frequency
is determined, the system will automatically disable the bypass function. Please note that,
once the inverter shuts down, there is no bypass output. During Frequency Conversion
mode, the UPS's tri-color LED illuminates green and the text 'Frequency Conversion'
appears in the upper right corner of the LCD screen.
Modulon DPH Series
(Figure 3-5: ECO Mode Diagram)
(Figure 3-6: Frequency Conversion Mode Diagram)
24