Use

The RDH 100 is used to control the room temperature in heating systems.

Typical applications:

  • Homes
  • Residential buildings
  • Schools
  • Offices

The device is used together with the following equipment:

  • Thermal valves or zone valves
  • Combi boilers
  • Gas or oil burners
  • Pumps

Functions

Temperature control

RDH100 offers both 2-position and PID intelligent learning temperature control, configurable via parameter P01 (control behaviour).
2-position control algorithm is to switch on and off the heating system within a switching differential (SD) as per difference between setpoint setting and measured room temperature.
Temperature control

PID intelligent learning control algorithm periodically switches on and off the heating system. The period time (T) and pulse length (P) of the control signal (PWM) are determined by the setpoint and the measured room temperature.
PID intelligent learning control
In general, PID control provides more comfort and is more energy efficient than 2-position control.

Control behaviour (P01)

The factory setting for control is "PID slow", ideal for most heating systems. Optimum control can be selected if control does not provide the desired result:

2-position, 1 K

2-position controller with 1 [K] switching hysteresis

  • For systems with small capacity that appear slow
  • For applications requiring extended runtimes or where frequent switching causes problems
  • For difficult control loops where hunting may result

Typical applications:

  • Dry floor heating systems
  • Heat pumps
  • Electric heating with contactors

2-position, 0.5 K

  • 2-position controller with 0.5 [K] switching hysteresis.
  • For general control situations. Provides better comfort than 1 [K] switching hysteresis.
  • Can also be used for difficult control situations.

PID slow
PID control behaviour for slow heating systems that require longer minimum On times and a limited number of switching cycles per hour.

Typical applications:

  • Wet floor heating systems, oil fired boilers
  • Can also be used for all other types of heating applications. (Alternative setting)
Minimum switch on/off time > 4 minutes
Minimum period Approximately 12 minutes

PID fast
PID control behaviour for fast heating systems that tolerate a high number of switching cycles.

Typical applications:

  • Electric heaters with current valve
  • Gas boilers
  • Fast thermal actuators
Minimum switch on/off time > 1 minute
Minimum period Approximately 6 minutes


Do not use PID fast for oil boilers or electric mechanical actuators!

Backup

When removing the batteries, the setpoints and information required for operating mode changeover are retained for max. 2 minutes.

Commissioning notes

Parameter list

Parameter Description Factory setting Setting range Remark
P01 Control behavior PID slow (4) 0 = 2P, 1.0 K
1 = 2P, 0.5 K
2 = PID fast
4 = PID slow
P02 Maximum temperature range 30°C P03...30°C Limit of comfort and economy setpoint
P03 Minimum temperature range 5°C 5°C...P02 Limit of comfort and economy setpoint
End Exit parameter setting

Parameter setting
The parameter setting remains in non-volatile memory and is not erased when the battery is removed. The reset function on the rear of the thermostat reloads the factory settings.

Parameter setting mode
  1. Press RESET on the rear for 5 seconds until "P01"appears.
    warning Note: Pressing the button longer than 10 seconds resets the thermostat.
  2. Press RESET again and the parameter value on secondline flashes and is ready for adjustment.
  3. Adjust the parameter using setting knob.
  4. Press RESET once to confirm the setting.
  5. Rotate the setting knob clockwise to next parameter andrepeat steps 2 to 4.
  6. Exit the parameter setting mode by rotating the setting knobclockwise to "End" and pressing the RESET button once.

warning Note: The thermostat automatically exits parameter setting mode one minute after the last action.

Equipment combinations

Description Product number Data sheet *)
Electrothermal actuator (for radiator valves) STA23.. 4884
Electrothermal actuator (for small valves 2.5mm) STP23.. 4884
Electromotoric actuator SFA21.. 4863

*) The documents can be http://siemens.com/bt/download.

Display

The digital display shows the current room temperature and the comfort temperature setpoint. When the heating output is active, the triangle symbol is displayed.

Ordering

When ordering, specify both name and product number, e.g. room temperature controller RDH100.
Order valves and actuators as separate items.

Mechanical design

The device consists of 3 parts:

  • Plastic housing with digital display containing the electronics, operating elements, and builtin room temperature sensor
  • Baseplate (mounting base)
  • Battery compartment

The housing engages in the baseplate and snaps on. The baseplate carries the screw terminals.
There is a reset button on the rear of the device.

Mechanical design

Elements 1 Display of the room temperature in °C / °F
2 Indicates a request for heating
3 Temperature setting knob
4 Battery compartment
5 Comfort temperature setpoint
6 Indicates low battery power; replace batteries

Product documentation

Topic Title Document ID:
Operating Operating instructions A6V101035984
Installation Mounting instructions A6V10974417
CE declaration A6V101123363

Related documents such as CE declaration, etc., can be downloaded at the following address: http://siemens.com/bt/download.

Notes

Mounting

When mounting the device, attach the baseplate first. Then, make the electrical connections, and fit and secure the device (refer to the separated mounting instructions A6V10974417). Mount the device on a flat wall and in compliance with local regulations.
If the reference room contains thermostatic radiator valves, set them to their fully open position.
Mounting

  • The devices are suitable for wall mounting.
  • Recommended height: 1.5 m above the floor.
  • Do not mount the devices in recesses, shelves, behind curtains or doors, or above or near heat sources.
  • Avoid direct solar radiation and drafts.
  • Seal the conduit box or the installation tube if any, as air currents can affect sensor readings.
  • Adhere to allowed ambient conditions.

Installation

No internal line protection for supply lines to external consumers.
Risk of fire and injury due to short-circuits!

  • Adapt the line diameters as per local regulations to the rated value of the installed overcurrent protection device.
  • The power supply lines must have an external circuit breaker with a rated current of max. 10 A.

Change of batteries

If the battery symbol appears, the batteries are almost empty and must be replaced.

Reset

To reset, press the reset button on the rear of the device. This resets all individual settings to their default values.

Maintenance

The device is maintenance-free.

Disposal


The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage.

  • Dispose of the device through channels provided for this purpose.
  • Comply with all local and currently applicable laws and regulations.
  • Dispose of empty batteries in designated collection points.

Instructions for the replacement of alkaline batteries

Explosion due to fire or short-circuit, even with discharged batteries
Risk of injury due to flying parts

  • Prevent the batteries from coming into contact with water.
  • Do not recharge batteries.
  • Do not damage or disassemble batteries.
  • Do not heat batteries over 85°C.


Leakage of electrolyte
Severe burns

  • Handle damaged batteries only wearing suitable protective gloves.
  • In case of contact with electrolyte, rinse eyes immediately with plenty of water. Consult a doctor.

Observe the following:

  • Use only a battery of the same type and from the same manufacturer as a replacement.
  • Observe the polarities (+/-).
  • The batteries must be new and undamaged.
  • Do not mix new and used batteries.
  • Store, transport and dispose of the batteries in compliance with local requirements, regulations and laws. Also observe the instructions of the battery manufacturer.

Technical data

Power supply
Operating voltage DC 3 V (2 x 1.5 V AA alkaline batteries)
Battery life >1 year (with AA alkaline batteries)
Internal sensor inputs
Thermistor 10 ± 1% at 25°C
Switching outputs (Lx, L1, L2)
Relay contacts Switching voltage Max. AC 250 V Min. AC 24 V
Switching current Max. 5 A res., 2 A ind.
At AC 250 V Min. 8 mA
Insulating strength Between relay contacts and coil AC 3,750 V
Between relay contacts (same pole) AC 1,000 V


No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line required under all circumstances.

Operational data
PID control: Slow Fast
Minimum period 4 min 2 min
Minimum pulse length 12 min 6 min
RDH100
Setpoint setting range 5...30°C
Factory setting comfort setpoint 20°C
RDH100/SPL
Setpoint setting range 15...30°C
Factory setting comfort setpoint 20°C
Resolution of settings and
displays
Temperature setpoint 0.5°C
Display of actual temperature value 0.5°C
Electrical connections
Connections terminals (via baseplate) Screw terminals
For solid wires 2 x 1.5 mm2
For stranded wires 1 x 2.5 mm2 (min. 0.5 mm2)

Environmental conditions

Operation IEC 60721-3-3
Climatic conditions Class 3K5
Temperature 0...+40°C
Humidity <90% r.h.
Transport IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -25...+60°C
Humidity <95% r.h.
Mechanical conditions Class 2M2
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature -10...+60°C
Humidity <90% r.h.

Standards, directives and approvals

EU conformity (CE) A6V101123363 *)
RCM conformity A6V11161600 *)
Safety class II as per EN 60730-1
Pollution degree 2
Degree of protection of housing IP20
Eco design and labeling directives Based on EU Regulation 813/2013 (Eco design directive) and 811/2013
(Labeling directive) concerning space heaters, the following classes apply:
Application with On/Off operation of a heater
Class I Value 1%
PWM (TPI) room thermostat, for use with
On/Off output heaters
Class IV Value 2%
Environmental compatibility The product environmental declaration (A6V101123358 *)) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).

*) The documents can be http://siemens.com/bt/download.

General

Weight (including package) 350 g
Color of housing front Signal-white RAL9003
Housing material ABS (LCD lens: PC)

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Siemens RDH100 - Room thermostat with large LCD Manual

Advertisement

Need Assistance?

Do you have a question about the RDH100 that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents