Setting A User Constant In The Basic Access Level - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

EXAMPLE

Setting a User Constant in the Basic Access Level

A
"
The function level will be displayed when the DATA/ENTER Key is pressed at the programming mode
display.
Use the following display to set the acceleration time to 20.0 s.
Step
Key Sequence
1
MENU
2
Press twice.
3
DATA
ENTER
4
5
6
DATA
ENTER
7
DATA
ENTER
8
RESET
Press twice.
9
10
DATA
ENTER
11
ESC
Returns to "Function C1 Accel/Decel" display.
Digital Operator Display
G5: Main Menu :
Operation
G5: Main Menu :
Programming
Function b1
Sequence
Function b2
DC Braking
Function C1
Accel/Decel
Accel Time 1
C1−01 = 10.0 Sec
Accel Time 1
0010.0 Sec
Accel Time 1
0010.0 Sec
Accel Time 1
0020.0 Sec
Entry Accepted
Accel Time 1
C1−01 = 20.0 Sec
Function C1
Accel/Decel
4 - 9
4.2 Modes
Remarks
Changed to constant reading (func-
tion) level.
Changed to constant setting level,.
Selects the user constant so that the
leading 0 blinks. The blinking digit
can be changed.
Blinking digit moves 2 places to the
right and the "1" blinks.
Changes 1 to 2.
Writes-in the new setting.
The Operator display is as shown on
the left.