Energy-Saving Control Function; Energy-Saving Gain: B8-01; Energy-Saving Frequency: B8-02; Hunting-Prevention Function - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

7.2.1 Energy-saving Control Function

The energy-saving control function is enabled when the energy-saving command (setting 63) has been set
in a multi-function input (H1-01 through H1-06). Inputting the energy-saving command while there is a
light load causes the Inverter's output voltage to be reduced and saves energy. Turn OFF the energy-saving
command when a normal load is added.

Energy-saving Gain: b8-01

J
User
User
Constant
Number
b8-01
Energy-saving gain
Constant b8-01 determines the Inverter's output voltage when the energy-saving command is input.
D
Set this value as a percentage of the V/f pattern's voltage.
Constant L2-04 (the voltage recovery time) determines the rate at which the output voltage is changed
D
when the energy-saving command is turned ON or OFF.

Energy-saving Frequency: b8-02

J
User
User
Constant
Number
Energy-saving fre-
b8-02
quency
Constant b8-02 determines the lower limit frequency for the energy-saving function.
D
The energy-saving command is enabled only when the frequency reference is above the energy-saving
D
frequency and the motor speed is within the "speed agree" range.
A time chart for energy-saving operation is shown below.
Run command
Energy-saving
command
Output frequency
Output voltage
Fig 7.5

7.2.2 Hunting-prevention Function

The hunting-prevention function suppresses hunting when the motor is operating with a light load. This
function is valid with V/f control and V/f with PG feedback control.
Hunting Prevention Selection: C7-01
J
User
User
Constant
Number
Hunting prevention
C7-01
selection
Change
g
during
during
Setting
Setting
Name
Opera-
Range
tion
0 to 100
×
Change
g
Setting
Setting
during
during
Name
Opera-
Range
tion
0.0 to 400.0
×
OFF
ON
OFF
ON
L2-04
(Voltage recovery time)
Time Chart for Energy-saving Operation
Change
g
during
during
Setting
Setting
Name
Opera-
Range
tion
0, 1
×
7 - 13
7.2 V/f Control without PG
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
%
80
A
A
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
Hz
0.0
A
A
Frequency reference ≥ b8-02
(energy-saving frequency)
E1-03 to E1-10 setting × Energy-saving Gain
(b8-01)
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
1
A
A
Open
Flux
Loop
Vector
Vector
×
×
Open
Flux
Loop
Vector
Vector
×
×
7
Open
Flux
Loop
Vector
Vector
×
×

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents