Carrier Frequency: C6-01 to C6-03

J
The carrier frequency characteristics differ according to the control method.
D
V/f control and V/f with PG feedback control: Carrier frequency variable setting possible.
Open-loop vector control and flux vector control: Constant frequency (The carrier frequency up-
per limit only is set.)
The carrier frequency does not normally need to be adjusted, but make adjustments in the following
D
cases:
If the wiring distance between the Inverter and the motor is long, lower the carrier frequency.
Wiring Distance
Carrier Frequency
If there are great irregularities in speed or torque, lower the carrier frequency.
User
User
Name
Constant
Number
Carrier frequency
C6-01
upper limit
Carrier frequency
C6-02
lower limit
Carrier frequency
C6-03
proportional gain
* 1. The setting range for the carrier frequency upper limit is as follows for the control methods:
S V/f control (with or without PG): 0.4 to 15.0
S Vector control (open-loop or flux): 2.0 to 15.0
* 2. The setting range and the factory setting vary according to the Inverter capacity. The table
shows a value of 200 V class, 0.4 kW. (See page 8 - 47.)
In the vector control modes, the carrier frequency is determined by the carrier frequency upper limit
D
(constant C6-01). In the V/f control modes (both with and without PG), the carrier frequency can be
changed in response to the output frequency by setting the carrier frequency lower limit (constant
C6-02) and the carrier frequency proportional gain (constant C6-03).
Carrier frequency
C6-01
C6-02
0
Fig 7.29

Setting the Carrier Frequency

To make the carrier frequency constant, either set the same value for constants C6-01 and C6-02 or
D
set the carrier frequency proportional gain (constant C6-03) to "0" (i.e., fix at upper limit value). The
following settings will generate a constant setting fault (OPE11):
Carrier frequency upper limit (C6-01) > 5.0 kHz and carrier frequency lower limit (C6-02) ≤ 5.0 kHz
Carrier frequency proportional gain (C6-03) > 6 and (C6-01) < C6-02)
If the lower limit is set higher than the upper limit, the lower limit will be disregarded and carrier frequency will
D
be fixed at the upper limit.
50 m max.
15 kHz max.
Change
g
during
during
Setting
Setting
Unit Factory
Opera-
Range
tion
*1
2.0 to 15.0
kHz
×
0.4 to 15.0
kHz
×
Mul-
00 to 99
×
tiple
Output frequency
x (C6-03) x K
E1-04
(Maximum output frequency)
7 - 56
100 m max.
Over 100 m
10 kHz
5 kHz max.
Valid Access Levels
Factory
Open
V/f
V/f with
Setting
Loop
Control
PG
Vector
*2
B
B
B
15.0
*2
A
A
15.0
×
A
A
00
×
The coefficient "K" varies depending
on the carrier frequency upper limit, as
described below:
D C6-01 ≥ 10.0kHz : K = 3
D 10.0kHz > C6-01 ≥ 5.0kHz : K = 2
D 5.0kHz > C6-01 : K = 1