Electronic Thermal Time Characteristics; Momentary Power Loss Settings: L2-01 To L2-05; Momentary Power Loss Detection: L2-01; Momentary Power Loss Ridethru Time: L2-02 - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

Electronic Thermal Time Characteristics

In this example, L1-02 is set to 1 minute, the motor is operating at 60 Hz, and general-purpose
motor characteristics (EI-02=0) are used.
Operating time (minutes)
10
7
3
1
0.4
0.1
0
Fig 7.46

Momentary Power Loss Settings: L2-01 to L2-05

J

Momentary Power Loss Detection: L2-01

User
User
Constant
Name
Number
Momentary power
L2-01
loss detection
Settings
D
Setting
0
Disabled. (An undervoltage fault is detected when there is a momentary power loss.)
Enabled. (Restarts if power is restored within the L2-02 time. An under-voltage fault is detected
1
for a longer power loss.)
Enabled during CPU operation. (Restarts if power is restored while the CPU is operating. An
2
undervoltage fault is not detected.)
This constant specifies the processing that is performed when a momentary power loss occurs.
D
When power loss ridethru is enabled (setting 1 or 2), operation will be restarted after a speed search
D
if the power is restored within the allowed time interval.
When power loss ridethru is disabled (setting 0), an undervoltage fault will be detected if power is in-
D
terrupted for more than 15 ms.

Momentary Power Loss Ridethru Time: L2-02

User
User
Constant
Name
Number
Momentary power
L2-02
loss ridethru time
The factory setting depends on the Inverter capacity. The factory setting shown in the table is for a 200
D
V class, 0.4 kW Inverter. (See page 8 - 47.)
This setting is valid only when constant L2-01 is set to 1. Set the power loss ridethru time in seconds.
D
100
150
200
Motor Protection Operating Time
Change
g
Setting
Setting
during
during
Range
Opera-
tion
0 to 2
×
Function
Change
g
during
during
Setting
Setting
Opera-
Range
tion
0.0 to 2.0
×
7 - 85
Cold start
Hot start
Motor current (%)
(E2-01 is 100%.)
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
0
B
B
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
B
B
s
0.7
Open
Flux
Loop
Vector
Vector
B
B
7
Open
Flux
Loop
Vector
Vector
B
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents