User Constant Access Levels - YASKAWA CIMR-MC5A20P4 Instruction Manual

Table of Contents

Advertisement

Setting User Constants

4.2.3 User Constant Access Levels

4.2.3 User Constant Access Levels
4
MC5
MC5
The VS-626MC5 has three access levels which divide the various user constants based on their applica-
tions, as shown below. The access level restricts which user constants can be set or displayed.
Quick-start
Basic
Advanced
Set the access level in initialize mode with user constant A1-01.
Changing the Access Level from Quick-start to Basic
J
The Inverter is set at the factory to start in the Quick-start access level. Use the following procedure to
change from the Quick-start level to the Basic level.
Step
Key Sequence
1
MENU
2
3
DATA
ENTER
4
5
DATA
ENTER
6
7
DATA
ENTER
As shown above, Quick-start has changed to Basic.
These seven steps can be illustrated as when in Figure 4.4.
MENU
Main Menu
Operation
DAT
A
ENTER
Main Menu
Initialize
Fig
4.4 Changing Quick-start to Basic
Allows reading/setting of user constants required for simple operation. (factory preset)
Allows reading/setting of Basic user constants.
Allows reading/setting of all user constants.
Digital Operator Display
MC5
Main Menu
Operation
MC5
Main Menu
Initialize
Select Language
English
Access Level
QUICK--START
A1- -01 = 2
QUICK--START
A1- -01 = 3
Basic
Entry Accepted
Access Level
Basic
Select Language
English
Access Level
QUICK--START
Access Level
Basic
- 6
Remarks
After approx. 3 seconds, the Operator
display is as shown on the left.
DAT
A
ENTER
A1- -01 = 2
QUICK--START
A1- -01 = 3
Basic
DAT
A
ENTER
Entry Accepted