FALSE FIREPLACE INSTALLATION

Framework of the installation MUST conform to local building codes. Non-combustible materials need not be
used. If the appliance is elevated from the ground within the structure, a base MUST be constructed using
suitable material with supporting joists capable of supporting a minimum of 1.5 times the weight of the appliance.
AS/NZS 5601 "GAS INSTALLATIONS" requires that flue components be supported independently
of the appliance.
CAUTION

ENCLOSURE DIMENSIONS

Enclosure dimensions are shown below. The enclosure dimensions specified are critical to the successful
installation of this appliance and MUST be strictly adhered to.
MASONRY
W1
H1
D
Level base with a slurry of sand
and cement.
Models
Height
Width
(H1)
(W1)
RDV600ER
600
600
RDV700ER
600
700
§ Framing MUST include supports for the mounting of the co-linear to coaxial flue adaptor.
The co-linear flexible flue MUST NOT come into contact with ANY combustible material.
WARNING
# The enclosure dimension for False Fireplace installations are larger, to make allowances for the
fitment of the zero clearance frame. The fitment of this frame is necessary to provide the required
clearances from any combustibles.
For clarity the consumer piping gas supply, electrical connections have been omitted, refer to
page 10 and page 11 for details. Construction details have also been simplified.
CAUTION
* As the heater engine is installed flush with the external surface, when preparing the cavity
the minimum depth needs to be inclusive of the external cladding thickness for false fireplace
installations. It is the installers responsibility that adequate clearance be provided between the
heater engine and any electrical connections on the inside of a masonry fireplace.
‡ Corner installations use False Fireplace enclosure dimensions and framing specifications.
In a masonry fireplace, use a slurry of sand and cement to level the base as required. Refer to
page 19 and page 20 for "False Fireplace Elevated Installation"
NOTE
Rinnai
Refer to Elevated Installation section.
Enclosure Type (All dimensions are minimums and are in mm unless otherwise stated)
Masonry
Depth
Chimney
Height
(D)
(X)
(H2)
400 *
200 x 200
700 #
400 *
200 x 200
700 #
FALSE FIREPLACE
Y
W2
H2
D
False Fireplace
Width
Depth
Support
(W2)
(D)
700 #
400 *
Max 600 §
800 #
400 *
Max 600 §
9

FRAMING

CORNER
Minimum internal dimensions
and clearances.
Corner ‡
Face
Sides
Depth
(Y)
(A)
(B)
1400
976
1500
1047
A
C
Clearance
(C)
(E)
676
25
726
25
RDV 600_700ER IM