Framing Dimensions - Rinnai RHFE1000 Installation Manual

Linear collection gas fireplaces
Hide thumbs Also See for RHFE1000:
Table of Contents

Advertisement

Framing dimensions

The framing dimensions have the studs offset. This is because the cavity needs to be
framed based on the centreline of the Linear glass, NOT the opening size.
IMPORTANT
Where there is a requirement for a symmetrical installation, the cavity size will need to
increase. To calculate a rough opening width, double the flue to centreline figure on the
following pages.
Base board and connection cutouts
To ensure everything lines up and fits properly it's recommended
that on the base the following dimensions are pencilled; glass
centreline, unit depth centreline, feet position, gas and room
thermistor cutouts.
Gas supply access
Thermistor / room supply air Ø 40 mm
A (room supply air)
B (gas supply)
C (support feet centres)
D (support feet centres)
E* (from front of cavity)
* E asssumes 10 mm wall board
Additional framing notes
Wallboard is set 1 mm back from the front edge of the lips to allow for a slim edge plaster finish.
To ensure the appliance performs correctly, without rattling, the Linear MUST BE installed on
a flat level support base. The joists must be capable of supporting a minimum of 1.5 times the
weight of the appliance—base panel is also designed to take the weight of the wallboard.
Issues caused by rattling fires not installed on a flat level base, as detailed in this guide,
will not be covered by warranty.
IMPORTANT
C
B
Linear 800
Linear 1000
50 mm
50 mm
220 mm
220 mm
640 mm
740 mm
360 mm
460 mm
77 mm
77 mm
Glass centreline
D
A
E
Linear 1500
255 mm
220 mm
990 mm
710 mm
77 mm
Linear installation guide 13563-H 08-19 | 13