6.7.5 Legend to the sequence diagrams

Valve proving takes place depending on the parameter:
Between phase 62 and phase 70 or / and between phase 24 and phase 30
1)
Parameter:
Short / long preignition time for oil only
Short / long oil pumps – switch-on time – time
2)
Only with valve proving on startup
3)
Parameter:
With / without alarm in the event of start prevention
4)
In the event of an erroneous signal on startup, followed by phase 10, otherwise phase 70
5)
28 s = maximum time safety phase, followed by lockout
6)
5 s = time between occurrence of start prevention and signaling
7)
Only with valve proving on startup (valve proving via pressure switch-min)
8)
Only without valve proving on startup (valve proving via pressure switch-min)
9)
Inverse logic with valve proving via pressure switch-min
10)
Parameter:
Oil pressure min input
1 = active from phase 38
2 = active from safety time
11)
Only with fuel train Lo and 2 fuel valves
12)
Repetition limitation pressure switch-min-gas in connection with gas shortage
Parameter 223:
program parameter 246 (phase 90)
13)
30 s = max. drop-in / response time for air pressure switch
Assignment of times:
t1
Prepurge time
t8
Postpurge time
t13
Permissible afterburn time
t44
Interval 1 gas / oil
t52
Interval 2 gas / oil
TSA1
Safety time 1 gas / oil
TSA2
Safety time 2 gas / oil
Permissible position range
In standby: The actuator can be moved within the permissible position range, but is always
driven to the no-load position. Phase changes necessitate the no-load position.
Position as supplied (0°)
90°
Actuator fully open (90°)
AL
Alarm
FS
Flame signal
KL
Low-fire position
LK
Valve proving
LP
Air pressure switch
M
Fan motor
N
Postpurge position / postpurging
P LT
Valve proving (pressure switch)
Pmin
Pressure switch-min
Pmax
Pressure switch-max
POC
Proof Of Closure
PV
Pilot valve
R
Control thermostat or pressurestat
SA...
Actuator
SA-R
No-load position
SA-V
High-fire position
SA-Z
Ignition position
SB
Safety limiter
SK
Safety loop
SV
Safety valve
V
High-fire position
V...
Fuel valve
Z
Ignition transformer
Signal ON
Signal OFF
Permissible signal
Basic documentation LMV37.4...