Siemens LMV37.4 Series Basic Documentation page 206

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Error
Diagnostic code
code
202
#
203
#
204
Phase number
205
#
206
0
207
#
0
1
208
#
209
#
210
0
240
#
245
#
250
#
206/213
Building Technologies
HVAC Products
Meaning for LMV37.4... system
Internal error operating mode selection
Internal error
Program stop
Internal error
Inadmissible combination of units
(basic unit - AZL2...)
Version compatibility basic unit - AZL2...
Basic unit version too old
AZL2... version too old
Internal error
Internal error
Selected operation mode is not released for the basic
unit
Internal error
Internal error
Internal error
Basic documentation LMV37.4...
28 Error code list
Recommended measures
Redefine the operating mode (parameter 201)
Redefine the operating mode (parameter 201).
Make a reset; if error occurs repeatedly, replace the unit
Program stop is active (no error)
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Select a released operation mode for the basic unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
CC1P7546en
01.12.2009