Restore - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Only
OEM
level
Building Technologies
HVAC Products
21.6.2

Restore

Basic documentation LMV37.4...
21 Operating the AZL2... unit
Parameter 000: blinks.
Display: Parameter 000: blinks, Int does not.
/reset
Press
to go to parameter group 041 .
/reset
Display: Parameter 041: blinks, ._._ does not.
Press
to select parameter 050
Display: Parameter 050. blinks, index 00: and value 0 do
not.
/reset
Press
to go to parameter bAC_UP
/reset
Display: Parameter bAC_UP
Press
to select parameter rEStorE
Display: Parameter rEStorE
/reset
Press
to select the restore process.
/reset
Display: Value 0
Press
to shift the value in change mode by one posi-
tion to the left.
Display: Value 1 blinks.
Note
To detect potential display errors, the value is displayed
one position shifted to the left.
127/213
CC1P7546en