Parameterizing Of The Vsd - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

102/213
Building Technologies
HVAC Products
11.10

Parameterizing of the VSD

If the burner's rated capacity is not reached at 95% (9.5 V) control, you can proceed as
follows:
Set the maximum frequency to 105.3% of the motor's rated speed
-
In the case of a motor frequency of 50 Hz, this means:
Set the maximum frequency of the VSD to 50 Hz x 1.053 = 52.6 Hz (on the VSD).
Then, standardize the speed (refer to section Standardizing the speed )
-
There is no risk of motor overload since only 95% of the maximum control signal is de-
livered during standardization and, later in operation, the actual speed is controlled and
monitored.
Frequencies of between 50 Hz and 52.6 Hz are delivered only if these are needed for
reaching the required speed due to increased output.
Set the ramp times of the VSD according to subsection Setting the ramp times
-
Basic documentation LMV37.4...
11 Fan control
CC1P7546en
01.12.2009