26.11.4 Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2
mod» and «Lo mod»)
Note
With the "warm settings", the burner is started up after pressing InFo . Air-fuel ratio control can
now be accurately set while the flame is present. When traveling along the precalculated curve
to high-fire point P9 , all intermediate curvepoints ( P2...P8 ) must be set.
Automatic operation is released when – after reaching P9 – the curve settings are quit by
pressing Esc . If the curve settings are aborted earlier ( Esc or shutdown due to fault), start
prevention OFF UPr continues to be active until all points are set.
If required, the gas pressure can be set at the high-fire point. In case the gas pressure is
changed, all points must be checked by traveling along the curve downward and – if required
– must be readjusted.
P
Note
If, during the time the curve is parameterized, an error occurs which leads to safety shutdown,
parameterization of the curve is quitted.
P
P
P
P
Building Technologies
HVAC Products
V
h min s
%
V
h min s
%
V
h min s
%
V
h min s
%
V
h
min s
%
Basic documentation LMV37.4...
26 Parameter level
Identification of start for setting the curve parameters.
When there is a request for heat.
/reset
Phase Standby (stationary)
Phase Fan ramp up (fan motor = ON, safety valve = ON)
Phase Traveling to prepurge
Phase Prepurging
position
163/213