25
Service level
The service level is used to display information about errors including the error history and information about
the basic unit.
25.1
Display of the service level
P
/reset
Building Technologies
HVAC Products
Note
When on the service level, you can press
ous parameter.
Instead of pressing
Note
ESC
Press
or
/reset
Note
P
V
h min s
Parameter
Parameter value
Figure 61: Service level
No change of values on the service level.
If characters
are displayed by the parameter, the value may consist of more
than 5 digits.
Press
for >1 s and <3 s to display the value.
/reset
Press
for >3 s or
/reset
(blinking).
V
h m in s
%
No.
Parameter
Service level
954
Flame intensity
960
Actual fuel throughput in unit of volume / h (m³/h, l/h, ft³/h, gal/h)
121
Manual output
Undefined = automatic operation
922
Incremental position of actuators
Index 0 = fuel
Index 1 = air
936
Standardized speed
161
Number of faults
701
Error history: 701-725.01.Code
.
.
.
725
Basic documentation LMV37.4...
25 Service level
or
, you can also press
/reset
for >3 s to return to the normal display.
%
ESC
to return to the selection of the parameter number
Press
for >3 s until SEr appears.
/reset
When releasing
, you are on the service level.
/reset
to display the next or the previ-
for <1 s.
139/213
CC1P7546en