Siemens LMV37.4 Series Basic Documentation page 183

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Par.
Parameter
no.
148
Performance standard at interruption of communication
with building automation
Setting values
For modulation operation the setting range is as fol-
lows:
0...19.9 = burner off
20...100 = 20...100% burner rating
For multistage operation apply to setting range:
0 = burner OFF, P1, P2, P3
Invalid = no performance standards of the building auto-
mation
Default setting: Invalid
161
Number of faults
162
Operating hours resettable
163
Operating hours when unit is live
164
Number of startups resettable
166
Total number of startups
167
Fuel volume resettable [m³, l, ft³, gal]
186
Software drop out delay of flame signal (100 ms)
Index = = QRB... / QRC... (0 = inactive, >1)
Index 1 = ION / QRA... (0 = inactive, >3 - only 200 ms-
steps)
Building Technologies
HVAC Products
Number of
Type
Edit
elements
1
Output
edit / clear
1
Std_u16
read only
1
Std_s32
reset
1
Std_s32
read only
1
Std_s32
reset
1
Std_s32
read only
1
Std_s32
reset
2
Std_u8
edit
Basic documentation LMV37.4...
27 Parameter list LMV37.4...
Value range
Resolution
Min
Max
0%
100%
0.1%
0
65535
1
0 h
9999999 h
1 h
0 h
9999999 h
1 h
0
9999999
1
0
9999999
1
0
99999999
1
0
20
1
Default
Password level
setting
undefined
SO (BA)
0
Info / Service
0 h
Info / Service
0 h
Info / Service
0
Info / Service
0
Info / Service
0
Info / Service
0; 0
OEM
183/213
CC1P7546en
01.12.2009