Siemens LMV37.4 Series Basic Documentation page 189

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Par.
Parameter
no.
500
Ratio control
501
No-flame positions fuel actuator
Index 0 = no-load position
Index 1 = prepurge position
Index 2 = postpurge position
502
No-flame positions air actuator
Index 0 = no-load position
Index 1 = prepurge position
Index 2 = postpurge position
503
No-flame speeds VSD
Index 0 = no-load speed
Index 1 = prepurge speed
Index 2 = postpurge speed
522
Ramp up
523
Ramp down
542
Activation of VSD / PWM fan
0 = inactive
1 = active
545
Lower output limit
undefined = 20 %
546
Upper output limit
undefined = 100 %
Building Technologies
HVAC Products
Number of
Type
Edit
elements
3
Std_s16
edit
3
Std_s16
edit
3
Std_s16
edit
1
Std_u8
edit
1
Std_u8
edit
1
Selection
edit
1
Output
edit / clear
1
Output
edit / clear
Basic documentation LMV37.4...
27 Parameter list LMV37.4...
Value range
Resolution
Min
Max
0 °
90 °
0.1 °
0 °
90 °
0.1 °
0%
100%
0.1%
5 s
20 s
1 s
5 s
20 s
1 s
0
1
1
20%
100%
0.1%
20%
100%
0.1%
Default
Password level
setting
0 °; 0 °; 15 °
SO
0 °; 90 °; 45 °
SO
0%; 100%; 50%
SO
10 s
SO
10 s
SO
0
SO
undefined
SO (BA)
undefined
SO (BA)
189/213
CC1P7546en
01.12.2009