Siemens LMV37.4 Series Basic Documentation page 114

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

114/213
Building Technologies
HVAC Products
No.
Parameter
Operating mode building automation
0 = off
141
1 = Modbus
2 = reserved
142
Setback time in the event of communication breakdown
Setting values
0 = deactivated
1...7200 s
148
Performance standard at interruption of communication with building automa-
tion
Setting values
For modulation operation the setting range is as follows:
0...19.9 = burner off
20...100 = 20...100% burner rating
For multistage operation apply to setting range:
0 = burner OFF, P1, P2, P3
Invalid = no performance standards of the building automation
Default setting: Invalid
The factory settings of the parameters are shown on the parameter list.
Note
For a detailed description of parameter 148, refer to section «Predefined output via
BAC system».
Basic documentation LMV37.4...
16 Connection to superposed systems
CC1P7546en
01.12.2009