Controller Logic Specifications - Kohler APM402 Operation

For industrial generator set 10-1000 kw
Table of Contents

Advertisement

Figure 8
AC Circuit Fuses in Control Box
F1 1 Amp. auto-resettable
Figure 9
Controller DC Fuses

1.3 Controller Logic Specifications

The controller logic specifications section is an overview of the various features and functions of the controller. Certain features
function only when optional accessories are connected. See the section titled: Operation, for details.
The default selection time delays and digital outputs are factory set and adjustable. Data entries require using a PC and
SiteTech™ software. See the SiteTech™ software operation manual for details.
Inhibit Time Delay. The inhibit time delay is the time period following crank disconnect during which the generator set stabilizes
and the controller does not detect a fault or status event. Select the desired inhibit time delay from 0 to 60 seconds.
Time Delay (Shutdown or Warning). The time delay follows the inhibit time delay. The time delay is the time period between
when the controller first detects a fault or status event and the controller warning or shutdown lamp illuminates. The delay
prevents nuisance alarms. Select the desired time delay from 0 to 60 seconds.
34
V7/V8/V9 fuses, 1.5 Amp. (qty. 3)
F2 1 Amp. auto-resettable
F3 12 Amp. non-replaceable
GM69407
GM6435-C
TP-6694
9/20