Two-Input/Five-Output Module - Kohler APM402 Operation

For industrial generator set 10-1000 kw
Table of Contents

Advertisement

6.1.6

Two-Input/Five-Output Module

The two-input/five-output module provides a generator set mounted panel with two analog or digital inputs and five digital outputs.
See Figure 70 for circuit board components and electrical connections to the controller.
See Figure 71 for connections of analog inputs.
See the following subsection, Accessory Connections, for terminal identification.
Use a computer with Kohler SiteTech™ software to assign functions to digital outputs. Each input and output corresponds to a
controller connection. Verify that the settings are appropriate for the connected sensor, switch, or equipment.
Refer to Introduction—List of Related Materials for the SiteTech™ Software Operation Manual part no.
SiteTech™ analog inputs B1 and B2 and digital outputs B1 through B5 are designated for use on the optional two-input/five-
output module. See Figure 69.
SiteTech I/O Name
Analog Input B1
Analog Input B2
Digital Output B1
Digital Output B2
Digital Output B3
Digital Output B4
Digital Output B5
Figure 69
Input/Output Assignments
P29/P30/P31 K1/K2/K3 2-amp relay outputs
P27 CAN
terminator
P26 RJ45 Out
P25 RJ45 In
(APM402/DEC
3000 P23)
Figure 70
Two-Input/Five-Output Module Board
P36
100 ohm min. or
50 mA max. current
0-5 Volt Ratiometric Sensor
Figure 71
Analog Input Connections P28
138
Optional I/O Module Connection
P28 Analog Input VN1/VP1
P28 Analog Input VN2/VP2
P29 (K1)
P30 (K2)
P31 (K3)
P32 (K4)
P32 (K5)
P28 In1/In2 analog or digital inputs
Optional 5 V Power
(50 mA max.)
+5
VPx
Analog
Device
VNx
GND
0-5 Volt Analog Device
P36
+5
VPx
Output
VNx
GND
GND
P32 K4/K5 10-amp relay outputs
P36
Optional 5 V Power
(50 mA max.)
+
Analog
Device
-
GND
+/- 3 Volt Analog Device
SW1 switch
+5
VPx
VNx
GND
TP-6694-6
TP-6694
9/20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Decision-maker 3000

Table of Contents