3.11.7 Battery

WARNING
Perform battery storage after all other storage procedures.
1.
Confirm that the generator set is stopped.
2.
Disconnect the battery(ies), negative (-) lead first.
3.
Clean the battery. Refer to the battery cleaning procedure.
4.
Place the battery in a cool, dry location.
5.
Connect the battery to a float/equalize battery charger or charge it monthly with a trickle battery charger. Refer to the
battery charger manufacturer's recommendations.
Maintain a full charge to extend battery life.
Note:
If the battery is an absorbed glass mat (AGM) type, ensure that the battery charger is compatible with AGM type batteries before
charging
TP-6694
9/20
Explosion.
Can cause severe injury or death.
Relays in the battery charger cause arcs or sparks.
Locate the battery in a well‐ventilated area. Isolate the battery charger from explosive
fumes.