Kohler APM402 Operation page 95

For industrial generator set 10-1000 kw
Table of Contents

Advertisement

For 180-500 RZXB/REZXB/REZXC/RZXD/REZXD (PSI/ Doosan 11.1L, 14.6L, 18.3L, and 21.9L Engines), use the following:
To change the fuel type, change the wiring harness connections. The engine ECM has fuel tables and spark advance curves
programmed for both natural gas and LPG. Use the following fuel connection lists and wiring diagrams to determine the
applicable connections for your generator set model. Be sure to review the wiring diagram for special applications.
Natural Gas with single fuel valve
See Figure 42.
Disconnect lead 70E.
Disconnect lead N6.
Disconnect lead N11 (250 – 500 kW only).
Disconnect lead N5.
Disconnect lead 65.
Disconnect lead 65A.
Disconnect lead 73B.
Connect lead 70B2 to fuel valve 1 (FV1), red/black wire.
For 250 – 500 kW (14.6 L – 22 L engines), connect lead 70B2 to fuel valve 1A (FV1A) and lead 70B2A to fuel
o
valve 1B (FV1B), red/black wires.
Connect lead 73A to fuel valve 1 (FV1), red/white wire.
For 250 – 500 kW (14.6 L – 22 L engines), connect lead 73A to fuel valve 1A (FV1A) and 73A1 to fuel valve 1B
o
(FV1B), red/white wires.
Connect lead N7 to fuel valve 1 (FV1), green wire.
For 250 – 500 kW (14.6 L – 22 L engines), connect lead N7 to fuel valve 1A (FV1A) and lead N10 to fuel valve
o
1B (FV1B), green wires.
Connect lead 63 to normally closed (NC), low fuel pressure sensor 1.
Connect lead N3 to common (COM), low fuel pressure sensor 1.
Natural Gas
180 – 200 kW (11 L)
ADV-7968-G
Figure 42
Natural Gas with Single Fuel Valve
TP-6694
9/20
250– 500 kW (14.6 – 22 L)
ADV-7994-K
95