6.1.14 Remote Reset Feature

The remote reset switch provides generator set controller resetting after a fault shutdown at a remote location. See Figure 79
and Figure 80 for user-supplied switch connection.
Press and hold the switch for 2-3 seconds and release to reset the generator set controller.
See the following subsection, "Accessory Connections," for terminal identifications.
Figure 79
Remote Reset Switch Connections
Switch Rating
Wiring Recommendation
Gauge
18-20
14
10
Figure 80
Switch Rating & Wiring Recommendations
144
Remote Reset Switch
Contacts Normally Open
Momentary Closed to Activate
Connect to TB1 as a Digital Input
12 volts DC minimum, 1 amp minimum
m (ft.)
30.5 (100)
153 (500)
305 (1000)
Battery Ground
TP-6694
9/20