Genset Information; Genset Run Time; Genset System - Kohler APM402 Operation

For industrial generator set 10-1000 kw
Table of Contents

Advertisement

2.7.5

GenSet Information

Displays generator set and controller information. Displayed data is factory entered.
GenSet Information
GenSet - - >
Information
2.7.6

GenSet Run Time

Displays the generator set's operating record including total run time loaded and unloaded, number of starts, and total energy
kW hours
GenSet Run Time
GenSet - - >
Run Time
2.7.7

GenSet System

Display shows the generator set system data including voltage, frequency, phase connection, etc. Use the values entered in this
menu to help determine shutdown values and time delays.
The programming user defines the data shown in the GenSet System menu. It is NOT data measured by the controller and
associated sensing devices. The programming user defines these values for purposes of calibrating the control.
Some alternators are designed to operate at limited voltage, frequency, or phase connections and as a result some settings may
have limited parameters:
Display for Measurement System is user selectable as English or Metric.
Contrast display is user adjustable to help improve digital display visibility in dimly lit rooms or in direct sunlight.
Note:
The contrast feature is a controller hardware change and may not be available on older units even if the firmware is updated.
The alarm (horn) silence display is programmer selectable to Always or Auto Only using SiteTech™ software. The Always
selection allows the alarm to be silenced in any of the OFF/RESET- AUTO- RUN modes. The Auto Only selection allows silencing
of the alarm only while in the Auto mode.
The manual speed adjustment is made using the Engine RPM menu. This feature is available as a factory-installed option or
requires a new factory personality profile. Adjustments can be made while the unit is running or stopped. To make adjustments,
press and hold the selector dial and the RPM display will start to flash. Then rotate the selector dial to the desired RPM and
press and hold the selector dial until the RPM display stops flashing. The adjustment range is 1751-1849 RPM (58-62 Hz) for
60 Hz and 1451-1549 RPM (48-52 Hz) for 50 Hz.
TP-6694
9/20
Genset M/N:
##
GenSet S/N:
##
Cntrllr S/N:
##
Eng Runtime:
##.# h
Eng Loaded:
#.# h
Eng Starts:
#
Total Energy:
#.# kWh
67