Kohler APM402 Operation page 134

For industrial generator set 10-1000 kw
Table of Contents

Advertisement

CAN connections (TB5-CAN (+)/-CAN (-)
TB5 output connections C and NO for the common
fault relay K15 (other TB5 terminals are factory
connections only)
Battery positive (+) connections (TB5-42A)
Figure 65
4-Input/15-Output Module Customer Connections
Connections
Leads 42A and 2 provide power to the relays. Do not use terminals 42A (+) or 2 (GND) on the controller connection kit terminal
strip to supply voltage to user-supplied accessories. User-supplied DC accessories require separate leads connected directly to
the battery for the voltage supply. Attach user-supplied 12/24-volt DC accessories to the battery positive (+) connection at the
starter solenoid and to the battery negative (-) connection at the engine ground. The 120 VAC accessories require a user-
supplied voltage source.
Note:
A maximum of three inputs may be connected to a single relay driver output. Inputs include dry contacts, remote annunciator,
common failure alarm, A/V alarm, and shunt trip line circuit breaker.
Note:
Only one 4-input/15-output module can be connected to the controller.
134
Battery negative (-) connections (TB5-2)
TB7 through TB13, connections for relays K1 through K14 with
Normally Open (NO) and Normally Closed (NC) contacts
P35 4-position jack connects to controller
(factory-connected)
TB6 8-position terminal block,
digital inputs/digital returns
(D11, D12, D13 and D14)
P36 8-position pin,
analog inputs
TP-6694
GM97144
9/20