Terminal Jumper - Kohler APM402 Operation

For industrial generator set 10-1000 kw
Table of Contents

Advertisement

P21 6-pin connector (for
RS-485 communications)
P23 8-pin connector (RJ45)
P30 jumper (Wound Field or
Fast Response)
Figure 6
Main Circuit Board Connectors
P21 (6-Pin) Connector for (RS-485) connection of optional RSA or Modbus
P23 (8-Pin) Connector (RJ45) for optional input/output (I/O) module circuit board.
Refer to the section titled: Accessory Connections for specific connections of the following terminal block connections.
TB1 (6-Position) Terminal Block for analog and digital inputs.
TB2 (4-Position) Terminal Block for K1 relay outputs.
TB3 (6-Position) Terminal Block for E-stop, remote start contacts, and aux. input connections.
1.2.7

Terminal Jumper

A circuit board P30 jumper is set based on alternator type—Wound Field (300 kW and larger) or Fast Response
(less than 350 kW). The jumper is factory set and needs no further adjustment. See the figure titled: Main Circuit Board
Connectors for location of the P30 jumper.
®
Modbus
is a registered trademark of Schneider Electric.
32
TB1 6-position terminal block
(4) push-on terminal connectors
P1 24-pin connector
®
communication.
TB2 4-position terminal block
TB3 6-position terminal block
GM102396
TP-6694
9/20