Kohler APM402 Operation page 27

For industrial generator set 10-1000 kw
Table of Contents

Advertisement

Event Log Menu
This menu allows the user to review up to 1000 entries of system events including shutdown faults, warning faults, and status
events. See the section titled: Controller Fault Diagnostics for a list of the items that appear on the Event Log.
Volt Select Menu
Note:
The generator set must be stopped before changing the voltage selection.
This menu allows the user to readily change controller voltage settings. The volt select feature is typically used in towable or
temporary applications.
Note:
The volt select menu requires initial activation by SiteTech™ software. In SiteTech™ software, select True to activate the volt
select menu.
Note:
The generator set output leads require voltage reconnection if the generator set does not have a voltage selector switch installed.
With the generator set stopped, go to the Volt Select menu. Then push and hold the pushbutton/rotary selector dial until the
voltage selection starts to flash. Volt selection is now available. Scroll to the desired voltage and momentarily press the
pushbutton/rotary selector dial to confirm the voltage selection.
The displays for Volt Select appear as shown in the following list.
120/240 V 1 Ph
120/208 V 3 Ph
139/240 V 3 Ph
277/480 V 3 Ph
120/240 V 3 Ph
TP-6694
9/20
27