Modular fire panel
Interfaces
A USB interface is provided to quickly transfer the required configuration to the panel
controller. There is also an Ethernet interface for adding the BIS software to the local network,
for example.
Saving and Printing Messages
Incoming messages and events are saved internally and can be viewed on the display. A log
printer for printing incoming messages can be connected.
2.2.2
FPE-8000-SPC | FPE-8000-PPC | FPE-2000-SPC | FPE-2000-PPC panel
controller
The panel controller is the central component of the fire panel. All messages are shown on the
color display. The entire system is operated via a touch screen. The user-friendly user interface
adapts to various situations. This allows correct operation that is both simple and clear as well
as targeted and intuitive.
The FSP-5000-RPS programming software enables adaption to project- and country-specific
requirements.
For operating the panel controller and the keypad refer to the user manual (F.01U.378.877)
available for download at www.boschsecurity.com.
Licenses
The panel controller is delivered with a hard coded software license. This software license is
implemented during production and cannot be modified, revoked or transported. The license
defines the maximum panel network size and availability of certain features and interfaces. In
total 4 different licenses are available.
Notice!
Building Management System
A premium license is required for each panel that needs to be available in a building
management system (e.g. BIS, FSM-5000-FSI). It is not sufficient to equip only one panel of
the network with a premium license, if you need all panels of the network in the building
management system.
Notice!
UGM-2040 hierarchy panel
A premium license is required for each panel that needs to be available in the UGM-2040
hierarchy panel. It is not sufficient to equip only one panel of the network with a premium
license, if you need all panels of the network in the hierarchy panel.
Notice!
Voice alarm system
Each fire panel which is physically connected to a voice alarm system (Praesideo, PAVIRO or
Plena) via Smart Safety Link needs a premium license.
Caution!
Do not use any pointed or sharp objects (e.g. screw drivers, pens, etc.) when operating the
!
touch-sensitive display. The touchscreen may not be exposed to direct sunlight. Both can
seriously damage the touchscreen.