Wiring; Connection Of Fk 100 Lsn Rf Interface Module To The Fire Panel - Bosch DOW 1171 Operation Manual

Radio frequency fire detection system
Table of Contents

Advertisement

18
en | Wiring
6

Wiring

6.1
Connection of FK 100 LSN RF Interface Module to the Fire
Panel
Notice!
The RF interface module requires a separate power supply of 24 V via the connections 0 V /
+U.
Figure 6.14: Interface Module Terminal Assignment
b2, a2
0V, +U
b1, a1
1.
2.
2016.04 | 6.0 | 4.998.120.885
b2 a2
LSN outgoing
20 to 30 V DC
Ground
LSN in
Remove the terminal blocks and wire up the connections.
Do not insert the terminal blocks until the RF interface module has been commissioned;
as this simplifies the commissioning procedure (see chapter Commissioning the FK 100
LSN RF Interface Module via WinPara / FSP-5000-RPS, page 21.
0V
+U
b1 a1 0V
Operation Guide
Radio Frequency Fire Detection System
+U