Modular fire panel
2.5

Housings for Wall Mounting

Figure 2.6: Housings for wall mounting
Wall mounting housings are screwed directly onto the wall. This reduces the installation depth
by approx. 9 cm, although the smaller 12 V/28 Ah batteries must be used as a result.
The modular system makes it easy to extend the system.
Housing Designs and Combinations
Two wall mounting housings are available as a base unit:
These housings can accommodate a panel controller with operating and display unit as the
central element.
The HCP 0006 A and HBC 0010 A basic housings can be extended to meet individual
requirements using:
Equipment Limits
The table below shows the maximum number of:
Housing type
HCP 0006 A
HBC 0010 A
HBE 0012 A
PSS 0002 A
PSB 0004 A
DIB 0000 A
Bosch Sicherheitssysteme GmbH
HCP 0006 A (for 6 modules), and
HBC 0010 A (for 10 modules)
HBE 0012 A Modular Extension Housing for an additional 12 modules, and 2 x 12 V/28 Ah
batteries
PSS 0002 A or PSB 0004 A Power Supply housings for additional power supply units and
12 V/28 Ah batteries
Modules
Panel rails (short PRS-0002-C, long PRD 0004 A)
Modules
Short rail
6
1
10
1
12
-
-
-
-
-
-
-
System Information
Product Description | en
21
Long rail
1
2
3
-
-
-
07.2020 | 12.0 | F.01U.028.089