Extended Line Monitoring (Vds 2540, Vds 2543); Fpp-5000 External Power Supply Unit Kit 24 V/6 A - Bosch FPA‑5000 System Information

Modular fire panel
Hide thumbs Also See for FPA‑5000:
Table of Contents

Advertisement

120 en | Installation
Type designation
Connection of ...
CBB 0000 A 1)
BCM Battery Controller
Module
CPA 0000 A
MPC Panel Controller
CPB 0000 A
BCM Battery Controller
Module
CPR 0001 A
MPC Panel Controller
CRP 0000 A
MPC Panel Controller
1) Required for power supply in a separate power supply housing. Compared to the enclosed standard cable sets,
this cable set has a longer connecting cable to the battery.
Notice!
In the installation instructions for the CPA 0000 A Cable Set: Please refer to the programming
instructions for the FMA-AT 2000‑IP/-ISDN/-GSM.
4.11

Extended line monitoring (VdS 2540, VdS 2543)

Auxiliary power supplies to the following modules can be monitored for creeping short circuits
and creeping open: LSN 0300 A, LSN 1500 A, and BCM-0000-B (when using FPP-5000-TI13). A
creeping short circuit is detected by these modules. An FPP-5000-TI13 forwards the faults
detected and reported by the BCM-0000-B to the panel. Use additional 4-wire end of line
elements to monitor for creeping open.
Procedure:
1.
2.
Notice!
VdS 2540, VdS 2543
For extended line monitoring (creeping short circuit and creeping open monitoring), no
branch wiring is permitted for auxiliary power supplies.
4.12
FPP‑5000 External Power Supply Unit Kit 24 V/6 A
The FPP-5000 External Power Supply Unit Kit is designed to provide a universal power supply,
and has space for two 12 V/45 Ah batteries.
Figure 4.73: FPP‑5000 External Power Supply Unit Kit 24 V/6 A
07.2020 | 12.0 | F.01U.028.089
... to
Monitor with 4-wire end of line element:
On stub cabling, terminate the exposed end of an AUX line with an FLM-420-EOL4W
Insert an FLM-420-EOL4W as the last element of an LSN ring or of a stub
Use an FLM-320-EOL4W-S for the conventional zone of a conventional zone module
or a FLM-420/4‑CON
In FSP-5000-RPS, activate operation with extended line monitoring (formerly EN 54-13
requirement, now VdS 2540 and VdS 2543 requirement).
Battery pair
FMA-AT 2000-IP/-ISDN/-GSM, ENO 0000 B F.01U.003.343
UPS Universal Power Supply
RLE 0000 A Junction Board
MPC Panel Controller (Redundant)
System Information
Modular fire panel
Document number
F.01U.003.099
F.01U.003.098
F.01U.003.342
F.01U.003.097
Bosch Sicherheitssysteme GmbH