Figure 2: Example 1 - Area Text; Figure 3: Example 2 - Custom Function; Programming The Control Panel - Bosch D1256 Installation Instructions Manual

Fire command center/fire alarm annunciators
Table of Contents

Advertisement

D1256/D1257
Installation
4.3

Programming the Control Panel

The Command Center, User Interface, Command Menu (D7212B1, D9112B1, and D9124 (using the D9112LTB)) or
Function List (D7212, D7212G, D7412, D7412G, D9112, D9412, D9412G and D9124 (using the D9112LTB-EX or
D9412GLTB)), and Passcode Worksheet sections of the control panel program determine the annunciator displays and
functions available from the D1256. Key points to consider are described in the remainder of this section.
4.3.1
Command Center Assignments
1.
Command Center Text. The D1256 can be used on any one of the eight addresses in the control panel.
Sections 4.3.2 through 4.3.4.2 describe programming for one D1256 assigned to Command Center #1.
2.
Supervised. Certain local jurisdictions may require that fire system annunciators be supervised. If this is a
requirement in your area, set supervision to YES for the addresses that use fire alarm annunciators.
3.
Scope. The D1256 is designed to acknowledge fire alarms and troubles, not burglar alarms and troubles. Set
the scope to include fire areas only.
4.
Area. Program the area number of the fire area(s) as normal.
4.3.2
Area Text
Area 1
Area # is On
P R E S S
Area # Not Ready
C H E C K
Area # is Off
* F I R E
Area # Acct is On
P R E S S
1.
Area # is On – PRESS ALARM SIL. Fire area should remain in the OFF state at all times. If the authority level is
not programmed correctly, the fire alarm area arms and PRESS ALARM SIL displays on the fire alarm
annunciator. Pressing the [ALARM SILENCE] key will both silence any alarm(s) and disarm the area. This causes the
fire alarm annunciator to show the normal * FIRE SYSTEM * display.
2.
Area # Not Ready – CHECK FIRE SYS. Most fire alarm areas consist of all 24-hour points and the Area # Not
Ready display is not used. If a controlled point type is used for some type of fire supervision device, and the device
becomes off-normal, CHECK FIRE SYS displays on the fire command center.
3.
Area # is Off - * FIRE SYSTEM *. This is the normal idle text for the fire alarm annunciator.
4.
Area # Acct is On - PRESS ALARM SIL. Fire area should remain in the OFF state at all times. If the authority
level is not programmed correctly, the fire alarm area arms and PRESS ALARM SIL displays on the fire alarm
annunciator. Pressing the [ALARM SILENCE] key silences any alarm(s) and disarms the area. This causes the fire
alarm annunciator to show the normal * FIRE SYSTEM * display.
4.3.3
Custom Function
Text
CF 128
A L A R M
CF 129
T R O U B L E
CF 130
D E T E C T O R
CF 131
A N U N C I A T O R
These items must be programmed as indicated in the Custom Functions section of Command Center to make the D1256
function keys operational. The passcode 125600 has been chosen for the following examples, although any passcode may
be used.
4.3.3.1 CF 128 – ALARM SILENCE ?
Key Stroke: [1][2][5][6][0][0][E]. This custom function is programmed as the first Menu item. It is executed when the
[ALARM SILENCE] key is pressed on the D1256. The key stroke entry of 125600E is seen by the control panel as a valid
passcode entry in the area having the authority level to silence a ringing fire bell in the area. The "E" at the end of the
string represents the [ENTER] key on the command center.
74-06925-000-H
A L A R M
S I L
F I R E
S Y S
S Y S T E M *
A L A R M
S I L
Figure 2: Example 1 – Area Text
S I L E N C E ?
S I L E N C E ?
R E S E T ?
R E S E T
Figure 3: Example 2 – Custom Function
D1256/D1257 Installation Instructions
Page 10
Area 2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1 2 5 6 0 0 E _ _ _ _ _ _ _ _ _
A 4 C C _ _ _ _ _ _ _ _ _ _ _ _
A 4 7 _ _ _ _ _ _ _ _ _ _ _ _ _
1 2 5 6 0 0 C _ _ _ _ _ _ _ _ _
© 2004 Bosch Security Systems

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D1257