154 en | Technical Data
Cable length
Number of LSN elements
LSN line current
Auxiliary supply AUX
(28 V DC)
Space required (H x W x D)
Weight
7.5.11
NZM 0002 A Notification Appliance Zone Module
Operating and display elements
Input voltage
Maximum current consumption
Maximum output voltage
Maximum output current
Space required (H x W x D)
Weight
7.5.12
RMH 0002 A Relay Module for mains voltage
Operating and display elements
Fuses
Input voltage
Feedback current
07.2020 | 12.0 | F.01U.028.089
LSN
AUX
Standby
Alarm
Standby mode (both zones)
In case of alarms (both zones)
For supply via panel rail
For external power supply
4 LEDs (2 x red, alarm/2 x yellow, fault)
2 buttons (each on/off)
F1 = T 6.3 A, F2 = T 6.3 A
20 V DC to 30 V DC
max. 8.5 mA per feedback output
1.7 x current consumption of the LSN elements
1.2 x auxiliary supply AUX
max. 3000 m, depending on configuration and cable type
Max. 127 LSN classic elements
Max. 254 LSN improved elements
max. 750 mA, depending on configuration and cable type
max. 1500 mA, depending on configuration and cable
type
max. 300 mA when connecting LSN classic elements
max. 500 mA for an LSN loop (ERT technology) or 2 x
max. 500 mA with 2 stubs
approx. 127 x 190 x 60 mm
approx. 440 g
4 LEDs (2 x red, alarm/2 x yellow, fault)
2 buttons (LED test)
20 V DC to 30 V DC
40 mA
65 mA + 500 mA per notification appliance
29.5 V DC
500 mA per notification appliance (in case of
alarm)
3 A per notification appliance (in case of
alarm)
approx. 127 x 96 x 60 mm
Approx. 135 g