150 en | Technical Data
Safety standards
Protection class
Alternative technical data is listed for the individual modules.
7.5.1
ANI 0016 A Annunciator Module
Display elements
Input voltage
Maximum current consumption
Space required (H x W x D)
Weight
7.5.2
BCM‑0000‑B Battery Controller Module
Input voltage
Current consumption at 23 V DC
Permissible battery capacities
Maximum current
Maximum load of fault outputs BAT
FAULT, AC FAULT and collective fault
Maximum battery resistance (fault
threshold)
Voltage outputs
Display and operating elements
07.2020 | 12.0 | F.01U.028.089
Standby mode (all LEDs off)
In case of alarm (all LEDs on)
Standby operation
Fault
with 2 batteries
with 4 batteries
of the module
to panel rails
for switch outputs
2 switchable outputs
1 green LED
3 yellow LEDs
EN 60950
IP 30
16 red LEDs, 16 yellow LEDs
20 V DC to 30 V DC
6 mA
26 mA
approx. 127 x 96 x 60 mm
approx. 206 g
20.4 V to 30 V
25 mA
40 mA
24 to 26 Ah, 36 to 45 Ah
48 to 52 Ah, 72 to 90 Ah
Max. 6 A
Max. 6 A
Max. 5.6 A (2 x 2.8 A cannot be connected in
parallel)
0 V/0 - 20 mA
430 mΩ
+24 V (20.4 - 30 V), 2.8 A, battery buffered
(programmable)
Mains power on
Mains fault /fault in battery 1/fault in battery 2