Configuration Of Bcm Battery Controller Module - Bosch FPA‑5000 System Information

Modular fire panel
Hide thumbs Also See for FPA‑5000:
Table of Contents

Advertisement

Modular fire panel
HCP 0006 A, Fully Configured Panel, with Installation Sequence
BCM-0000-B
Figure 3.7: Example of configuration with HCP 0006 A Modular Panel Housing for 6 Modules
3.10

Configuration of BCM Battery Controller Module

The panel can be powered by up to 8 BCM-0000-B Battery Controller Modules, each with its
own UPS 2416 A Universal Power Supply. Current consumption is equally distributed among
all battery controller modules.
Notes
Bosch Sicherheitssysteme GmbH
9
2
PRS-0002-C
PRD 0004 A
10
<= 4 Module
FPO-5000-PSB-CH
1
8
UPS 2416 A
The 24 V switch outputs may not be connected in parallel.
The total current for all connected components including the battery charge current may
not exceed 6 A.
MPC
5
3
System Information
Planning | en
RLU 0000 A
HCP 0006 A
6
7
12 V / 28 Ah
12 V / 28 Ah
07.2020 | 12.0 | F.01U.028.089
43
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fpa‑1200

Table of Contents