Detection Points - Bosch FPA‑5000 System Information

Modular fire panel
Hide thumbs Also See for FPA‑5000:
Table of Contents

Advertisement

Modular fire panel
Refer to
3.2

Detection Points

Each element or input that can trigger an alarm counts as an detection point. One stand-alone
panel manages up to 4096 detection points. A panel operated in a network is limited to 2048
points.
All elements and inputs that do not use the Input type in the Message type setting are
regarded as detection points. Therefore, all elements and inputs for which one of the
following settings is programmed as the Message type are regarded as detection points:
Only some of these message types are available for selection depending on the element type.
The elements and inputs that can trigger an alarm include all manual and automatic detectors,
as well as the modules and interface modules listed below on the basis of the available inputs.
Modules
CZM 0004 A
IOP 0008 A
RMH 0002 A
ENO 0000 B
FPP‑5000‑TI
Interface Modules
FLM-420/4CON
Bosch Sicherheitssysteme GmbH
Limits per LSN 0300 module:
Up to 127 LSN classic elements or 254 LSN improved elements can be connected
Current consumption of up to 300 mA
Cable length of up to 1600 m
Limits per LSN 1500 module:
Up to 127 LSN classic elements or 254 LSN improved elements can be connected
Up to 1500 mA current consumption if LSN improved elements are connected
Up to 300 mA current consumption if LSN classic elements are connected
Cable length of up to 3000 m
As stipulated by EN 54‑2, panels with more than 512 LSN elements must be equipped
with a redundant panel controller.
Detection Points, page 29
Redundancy, page 34
Achievable Cable Length with LSN 0300 A, page 36
Fire
Internal fire
Supervisory
Multi-criterion
Smoke
Fault
Heat
Water
Detection Points
Up to 4 (1 detection point per zone)
Up to 8 (1 detection point per monitored input)
Up to 2
requires 1 detection point only if a FSE release element is
connected and programmed using the FSP-5000-RPS
programming software
2
Detection Points
Up to 2
System Information
Planning | en
29
07.2020 | 12.0 | F.01U.028.089